The KYN28A indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 3.6kV-12kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the instrument panel of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, and controlling the on-site network via a bus with communication interfaces. It also provides the "five preventions" functions: prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch when energized, prevention of energizing with the earthing switch in the earthed position, and prevention of mistakenly entering an energized compartment.

Request a quote

Please provide your operating conditions, quantity and required connection or output.

Technical details

Specifications from source material

The KYN28A indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 3.6kV-12kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the instrument panel of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, and controlling the on-site network via a bus with communication interfaces. It also provides the "five preventions" functions: prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch when energized, prevention of energizing with the earthing switch in the earthed position, and prevention of mistakenly entering an energized compartment.

Ambient air temperature
upper limit +40℃
Altitude
1000m. 3
Humidity
relative humidity: daily average not more than 95%, monthly average not more than 90%. 4
Water vapor pressure
daily average not more than 2.2kPa, monthly average not more than 1.8kPa. 5. When temperature drops sharply, condensation may occur, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions. a. Infrequent condensation (not more than twice per month on average) with light pollution. b. Generally no condensation (not more than twice per month on average) with relatively severe pollution. 6. Locations without fire or explosion hazards and without severe pollution, such as gases capable of corroding metals and damaging insulation. 7. Locations without severe vibration, jolting, or vertical inclination not exceeding 8°
Note
*Storage and transport at -30℃ is permitted. For areas with altitude above 2000m, handle according to "Technical Requirements for High Voltage Apparatus for Plateau Use under Special Environmental Conditions (GB/T 20635-2006)". When altitude does not exceed 2000m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate
Rated operating voltage
kV 12
Rated operating current
A 630, 1250, 1600, 2500, 3150, 4000
Rated frequency
Hz 50
Rated short-circuit breaking current
kA 20, 25, 31.5, 40, 50
Rated short-circuit making current (peak)
kA 50, 63, 80, 100, 125
Rated short-time withstand duration
S 4
Rated short-time withstand current
kA 20, 25, 31.5, 40, 50
Rated peak withstand current
kA 50, 63, 80, 100, 125
Rated short-time power frequency withstand voltage
kV/1min 42
Rated lightning impulse withstand voltage
kV 75, 95
Rated short-time power frequency withstand voltage (across open contacts)
kV/1min 48
Rated short-time power frequency withstand voltage (across open contacts)
kV/1min 48
Rated lightning impulse withstand voltage (across open contacts)
kV 85, 110

Full product details

Overview

The KYN28A indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 3.6kV-12kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the instrument panel of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, and controlling the on-site network via a bus with communication interfaces. It also provides the "five preventions" functions: prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch when energized, prevention of energizing with the earthing switch in the earthed position, and prevention of mistakenly entering an energized compartment.

Operating Environment

1. Ambient air temperature: upper limit +40℃; lower limit -10℃ in general areas. 2. Altitude: 1000m. 3. Humidity: relative humidity: daily average not more than 95%, monthly average not more than 90%. 4. Water vapor pressure: daily average not more than 2.2kPa, monthly average not more than 1.8kPa. 5. When temperature drops sharply, condensation may occur, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions. a. Infrequent condensation (not more than twice per month on average) with light pollution. b. Generally no condensation (not more than twice per month on average) with relatively severe pollution. 6. Locations without fire or explosion hazards and without severe pollution, such as gases capable of corroding metals and damaging insulation. 7. Locations without severe vibration, jolting, or vertical inclination not exceeding 8°. Note: *Storage and transport at -30℃ is permitted. For areas with altitude above 2000m, handle according to "Technical Requirements for High Voltage Apparatus for Plateau Use under Special Environmental Conditions (GB/T 20635-2006)". When altitude does not exceed 2000m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate.

Technical Parameters

Rated operating voltage: kV 12; Rated operating current: A 630, 1250, 1600, 2500, 3150, 4000; Rated frequency: Hz 50; Rated short-circuit breaking current: kA 20, 25, 31.5, 40, 50; Rated short-circuit making current (peak): kA 50, 63, 80, 100, 125; Rated short-time withstand duration: S 4; Rated short-time withstand current: kA 20, 25, 31.5, 40, 50; Rated peak withstand current: kA 50, 63, 80, 100, 125; Rated short-time power frequency withstand voltage: kV/1min 42; Rated lightning impulse withstand voltage: kV 75, 95; Rated short-time power frequency withstand voltage (across open contacts): kV/1min 48; Rated short-time power frequency withstand voltage (across open contacts): kV/1min 48; Rated lightning impulse withstand voltage (across open contacts): kV 85, 110; Protection class IP4X (customizable)

Overall Dimensions

Height (measured to the header)/mm 2300; Width (outer frame)/mm 800, 1000; Depth (outer frame)/mm 1500; Weight (kg)/mm 800~1200

Product Features

The switchgear consists of two main parts: a fixed cabinet and a withdrawable part (referred to as the handcart). The cabinet enclosure and the partitions of each functional unit are bolted together using aluminum-zinc coated steel sheets. The enclosure protection class of the switchgear reaches IP4X; the protection class is IP2X when the compartment partitions are loose and when the circuit breaker compartment door is open. Main features: 1. The cabinet structure is of assembled type, and the circuit breaker adopts a floor-standing handcart structure. 2. Equipped with a new type of composite-insulated vacuum circuit breaker, featuring good interchangeability and easy replacement. 3. The handcart frame is equipped with a screw-nut propulsion mechanism, allowing easy movement of the handcart and preventing incorrect operation from damaging the propulsion structure. 4. All operations can be performed with the cabinet door closed. 5. The interlocks among the main switch, handcart and switchgear door adopt forced mechanical closure, satisfying the "five preventions" functions. 6. The cable compartment has ample space and can connect multiple cables. 7. Quick earthing switch is used for earthing and circuit short-circuiting. 8. Enclosure protection class IP4X; with the handcart compartment door open, protection class IP2X. Enclosure and partitions: The enclosure and partitions of the switchgear are made of high-quality imported aluminum-zinc coated steel sheets, processed by CNC machine tools, bent and bolted together, so that the assembled switchgear maintains dimensional uniformity. It has strong corrosion and oxidation resistance and higher mechanical strength than equivalent steel sheets. The switchgear is divided by partitions into the handcart compartment (circuit breaker compartment), busbar compartment, cable compartment and instrument compartment (low-voltage compartment). The enclosure of each unit is independently earthed. Cabinet: The cabinet enclosure and partitions of the switchgear are made of aluminum-zinc coated steel sheets or steel sheets processed and bent by CNC machine tools and bolted together, so that the assembled switchgear maintains dimensional uniformity. The aluminum-zinc coated steel sheet has strong corrosion and oxidation resistance and higher mechanical strength than equivalent steel sheets. The switchgear is divided by partitions into the handcart compartment, busbar compartment, cable compartment and instrument compartment, and the enclosure of each unit is independently earthed. The doors of the switchgear are electrostatic spray coated, giving the surface impact resistance, corrosion resistance and an attractive appearance (color can be specified by the user). Busbar compartment: Busbars are led from one switchgear to another and fixed via branch busbars and static contact boxes. The flat branch busbars are bolted to the static contact boxes and main busbars without any other clamps or insulators. When required by the user and special engineering needs, the connecting bolts on the busbars can be encapsulated with insulation and end caps. When busbars pass through the switchgear partitions, they are fixed with busbar bushings. In the event of an internal fault arc, it can limit the spread of the accident to adjacent cabinets and ensure the mechanical strength of the busbars. Pressure relief device: Pressure relief devices are provided above the handcart compartment, busbar compartment and cable compartment. When an internal fault arc occurs in the circuit breaker, main busbar or cable compartment, along with the arc, the internal pressure of the switchgear rises; after reaching a certain pressure, the pressure release metal plate on the top device will open automatically to release pressure and exhaust gas, ensuring the safety of operators and the switchgear. Instrument compartment: The instrument compartment is used to install components such as integrated protection devices, meters, signal relays, signal indicators, operating switches, maintenance test links, position indicator lights, opening/closing status indicator lights and live-line indicators. In addition, a small busbar compartment can be added on top of the instrument compartment as required by the user, where sixteen control small busbars can be laid.