High-voltage series
KYN61
The KYN61 indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 40.5kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the compartment panels of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, controlling the site network via a bus with communication interfaces. It also provides prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch while energized, prevention of energizing the earthing switch in the earthed position, and prevention of entering energized compartments, i.e. the "five preventions" functions.
Request a quotePlease provide your operating conditions, quantity and required connection or output.
Technical details
Specifications from source material
The KYN61 indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 40.5kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the compartment panels of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, controlling the site network via a bus with communication interfaces. It also provides prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch while energized, prevention of energizing the earthing switch in the earthed position, and prevention of entering energized compartments, i.e. the "five preventions" functions.
- Ambient air temperature
- upper limit +40°C, lower limit -10°C in general areas
- Altitude
- 1000m
- Humidity
- relative humidity: daily average not more than 95%, monthly average not more than 90%
- Water vapor pressure
- daily average not more than 2.2 kPa, monthly average not more than 1.8 kPa. Condensation may occur when temperature drops sharply, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions. a. Infrequent condensation (not more than twice per month on average) with light pollution. b. Generally no condensation (not more than twice per month on average) with relatively severe pollution. Locations without fire or explosion hazards and without severe pollution or gases capable of corroding metals and damaging insulation. Locations without severe vibration, shock, or vertical inclination not exceeding 8°
- Note
- * Storage and transport at -30°C is permitted. For areas with altitude above 2000m, handle according to the "Technical requirements for high-voltage apparatus for plateau special environmental conditions (GB/T 20635-2006)". When altitude does not exceed 2000m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate
- Rated operating voltage
- kV 40.5
- Rated operating current
- A 1250, 1600, 2000, 2500
- Rated frequency
- Hz 50
- Rated short-time withstand current (earthing device)
- kA 25, 31.5, 40, 50
- Rated peak withstand current (earthing device)
- kA 63, 80, 100, 125
- Rated short-circuit duration
- S 4
- Rated short-time withstand current (earthing circuit)
- kA 27.4, 34.6, 43.3
- Rated peak withstand current (earthing circuit)
- kA 69.6, 86.6, 108.3
- Rated short-time power-frequency withstand voltage
- kV 95
- Rated lightning impulse withstand voltage
- kV 185. Rated short-time power-frequency withstand voltage (across open contacts): kV 118. Rated lightning impulse withstand voltage (across open contacts): kV 215. Degree of protection IP4X (customizable)
Full product details
Overview
The KYN61 indoor metal-clad withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete power distribution unit, used to receive and distribute 40.5kV network power and to control, protect and monitor circuits. Various types of microprocessor-based integrated relay protection devices can be installed on the compartment panels of this product, enabling intelligent system control with remote control, remote measurement, remote signaling and remote adjustment functions, controlling the site network via a bus with communication interfaces. It also provides prevention of incorrect circuit breaker operation, prevention of withdrawing or inserting the handcart under load, prevention of closing the earthing switch while energized, prevention of energizing the earthing switch in the earthed position, and prevention of entering energized compartments, i.e. the "five preventions" functions.
Operating environment
Ambient air temperature: upper limit +40°C, lower limit -10°C in general areas. Altitude: 1000m. Humidity: relative humidity: daily average not more than 95%, monthly average not more than 90%. Water vapor pressure: daily average not more than 2.2 kPa, monthly average not more than 1.8 kPa. Condensation may occur when temperature drops sharply, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions. a. Infrequent condensation (not more than twice per month on average) with light pollution. b. Generally no condensation (not more than twice per month on average) with relatively severe pollution. Locations without fire or explosion hazards and without severe pollution or gases capable of corroding metals and damaging insulation. Locations without severe vibration, shock, or vertical inclination not exceeding 8°. Note: * Storage and transport at -30°C is permitted. For areas with altitude above 2000m, handle according to the "Technical requirements for high-voltage apparatus for plateau special environmental conditions (GB/T 20635-2006)". When altitude does not exceed 2000m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate.
Technical parameters
Rated operating voltage: kV 40.5. Rated operating current: A 1250, 1600, 2000, 2500. Rated frequency: Hz 50. Rated short-time withstand current (earthing device): kA 25, 31.5, 40, 50. Rated peak withstand current (earthing device): kA 63, 80, 100, 125. Rated short-circuit duration: S 4. Rated short-time withstand current (earthing circuit): kA 27.4, 34.6, 43.3. Rated peak withstand current (earthing circuit): kA 69.6, 86.6, 108.3. Rated short-time power-frequency withstand voltage: kV 95. Rated lightning impulse withstand voltage: kV 185. Rated short-time power-frequency withstand voltage (across open contacts): kV 118. Rated lightning impulse withstand voltage (across open contacts): kV 215. Degree of protection IP4X (customizable).
Overall dimensions
Height (measured to the lintel)/mm 2600. Width/mm 1400, 1600. Depth (outer frame)/mm 2800. Weight/kg 1500~2000.
Product features
The switchgear consists of two main parts: a fixed cabinet body and withdrawable components (referred to as handcarts). The enclosure of the cabinet body and the partitions of each functional unit are bolted together from aluminum-zinc coated steel sheets. The enclosure protection degree of the switchgear reaches IP4X; the protection degree of the partitions between compartments and when the circuit breaker compartment door is open is IP2X. Main features: The cabinet structure is of assembled type, and the circuit breaker adopts a floor-standing handcart structure; equipped with a new type of composite-insulation vacuum circuit breaker, featuring good interchangeability and easy replacement; the handcart frame is fitted with a screw-nut propulsion mechanism, allowing easy movement of the handcart and preventing incorrect operation from damaging the propulsion structure; all operations can be performed with the cabinet doors closed; the interlocks among the main switch, handcart and switchgear doors all use forced mechanical locking to satisfy the "five preventions" functions; the cable compartment has ample space and can connect multiple cables; the quick earthing switch is used for earthing and circuit short-circuiting; enclosure protection degree IP4X, protection degree IP2X with the handcart compartment door open. Enclosure and partitions: The enclosure and partitions of the switchgear are made of high-quality imported aluminum-zinc coated steel sheets, processed by CNC machine bending and then bolted together, so that the assembled switchgear maintains dimensional uniformity. It has strong corrosion and oxidation resistance and higher mechanical strength than equivalent steel sheets. The switchgear is divided by partitions into the handcart compartment (circuit breaker compartment), busbar compartment, cable compartment and instrument compartment (low-voltage compartment). The enclosure of each unit is independently earthed. Cabinet body: The cabinet body enclosure and partitions of the switchgear are made of aluminum-zinc coated steel sheets or steel sheets processed and bent by CNC machines and then bolted together, so that the assembled switchgear maintains dimensional uniformity. The aluminum-zinc coated steel sheet has strong corrosion and oxidation resistance and higher mechanical strength than equivalent steel sheets. The switchgear is divided by partitions into the handcart compartment, busbar compartment, cable compartment and instrument compartment; the enclosure of each unit has independent earthing. The doors of the switchgear are electrostatically powder-coated, giving the surface impact resistance, corrosion resistance and an attractive appearance (color can be specified by the user). Busbar compartment: Busbars are led from one switchgear to another and fixed via branch busbars and static contact boxes. The flat branch busbars are bolted to the static contact boxes and main busbars without any other clamps or insulators. For special user and project requirements, the connecting bolts on the busbars can be encapsulated with insulation and end caps. Where busbars pass through switchgear partitions, they are fixed with busbar bushings. In the event of an internal fault arc, the spread of the fault to adjacent cabinets can be limited, and the mechanical strength of the busbars can be ensured. Pressure relief device: Pressure relief devices are provided above the handcart compartment, busbar compartment and cable compartment. When an internal fault arc occurs in the circuit breaker, main busbar or cable compartment, along with the arc the internal pressure of the switchgear rises; after reaching a certain pressure, the pressure-release metal plate on the top device opens automatically to release pressure and exhaust gas, ensuring the safety of operators and the switchgear. Instrument compartment: The instrument compartment is used to install components such as integrated protection devices, meters, signal relays, signal indicators, operating switches, test links, position indicator lights, opening/closing status indicator lights and live-line indicators. In addition, as required by the user, a small busbar compartment can be added at the top of the instrument compartment, where sixteen control small busbars can be laid.